WSC2 1800 PF |
WSC2 2200 PF |
WSC2 2800 PF |
WSC2 4100 PF |
WSC2 5500 PF |
Koelcapaciteit [W] ¹ |
1800/1600 |
2200/1900 |
2800/2300 |
4100/3400 |
5500/4600 |
Kamervolume tot [m³] |
30 |
40 |
55 |
90 |
130 |
Koelbereik in de koelcel [˚C] |
+5 to +20 |
+5 to +20 |
+5 to +20 |
+5 to +20 |
+5 to +20 |
Toelaatbare omgevingstemperatuur [˚C] |
-15 to +43 |
-15 to +43 |
-15 to +43 |
-15 to +43 |
-15 to +43 |
Koudemiddel / GWP |
R513A/573 |
R513A/573 |
R513A/573 |
R513A/573 |
R513A/573 |
geluidsdruk [dB(A)] ³ |
34/34 |
34/34 |
39/36 |
40/37 |
40/37 |
Voltage [V] / Phases / Frequency [Hz] |
230/1/ 50 |
230/1/ 50 |
400/3/50 |
400/3/50 |
400/3/50 |
Ontdooien type |
Circulerende lucht |
Circulerende lucht |
Circulerende lucht |
Circulerende lucht |
Circulating air |
Afmetingen condensorunit H x B x D |
600x900x350 |
600x900x350 |
840x1030x425 |
840x1030x425 |
840x1030x425 |
Afmetingen verdamper H x B x D |
455x752x430 |
455x752x430 |
455x752x430 |
455x1212x430 |
455x1212x430 |
¹ Condensorunit; verdampingstemperatuur; omgevingstemperatuur; verdamper superheat; invloeden van de installatielocatie en andere koelcomponenten moeten afzonderlijk worden bekeken
² Basis voor de berekeningen voor celgrootte: Celtemperatuur:, omgevingstemperatuur, warmteafgifte van goederen, bedrijfstijd, goederenbehandeling, inspectie en verlichting
³ Max. compressor inlaat superheat
⁴ Gebaseerd op AR5 / IPCC
⁵ Gewogen geluidsdruk op een afstand van 10 m
|
WSC2 1700 PM |
WSC2 2100 PM |
WSC2 2600 PM |
WSC2 3700 PM |
WSC2 5100 PM |
WSC2 6400 PM |
Cooling capacity [W]¹ |
1700/1400 |
2100/1800 |
2600/2100 |
3700/3100 |
5100/4300 |
6400/5400 |
Room volume up to [m³]² |
25 |
35 |
45 |
70 |
105 |
140 |
Cold room tempe- rature adjustment range [°C] |
+2 to +20 |
+2 to +20 |
+2 to +20 |
+2 to +20 |
+2 to +20 |
+2 to +20 |
Allowed ambient temperature [° C] ³ |
-15 to +43 |
-15 to +43 |
-15 to +43 |
-15 to +43 |
-15 to +43 |
-15 to +43 |
Refrigerant / GWP ⁴ |
R513A/573 |
R513A/573 |
R513A/573 |
R513A/573 |
R513A/573 |
R513A/573 |
Sound pressure level day / night [dB(A)] ⁵ |
34/34 |
34/34 |
39/36 |
40/37 |
40/37 |
41/38 |
Voltage / Phases / Frequency (V/-/Hz) |
230/1/50 |
230/1/50 |
400/3/50 |
400/3/50 |
400/3/50 |
400/3/50 |
Defrosting type |
Electrical |
Electrical |
Electrical |
Electrical |
Electrical |
Electrical |
Dimensions condensing unit HxWxD [mm] |
600x900x350 |
600x900x350 |
840x1030x425 |
840x1030x425 |
840x1030x425 |
1245x1030x425 |
Dimensions evaporator HxWxD [mm] |
455x752x430 |
455x752x430 |
455x752x430 |
455x1212x430 |
455x1212x430 |
455x1672x430 |
¹ Condensing unit, Evaporation temperature t₀ -7°C; ambient temperature + 32°C / 43°C; evaporator superheat 10K; influences of installation location and other refrigeration circuit components must be considered independently
² Basis of calculation for room size: Room temperature +2°C, Ambient temperature +25°C, heat extraction from goods 15K, operating time 16 h/day, goods handling 1/7 per day, inspection and lighting 0.5 h / day
³ Max. Compressor inlet superheat 20K
⁴ Based on AR5 / IPCC
⁵ Condensing unit, A-weighted equivalent sound pressure level at a distance of 10m
|
WSC2 2100 FV |
WSC2 2700 FV |
WSC2 3400 FV |
WSC2 5000 FV |
WSC2 6700 FV |
Cooling capacity [W]¹ |
2100/1800 |
2700/2300 |
3400/2800 |
5000/4200 |
6700/5700 |
Room volume up to [m³]² |
35 |
50 |
65 |
105 |
150 |
Cold room temperature adjustment range [°C] |
+5 to +20 |
+5 to +20 |
+5 to +20 |
+5 to +20 |
+5 to +20 |
Allowed ambient tem-perature [°C] ³ |
-15 to +43 |
-15 to +43 |
-15 to +43 |
-15 to +43 |
-15 to +43 |
Refrigerant / GWP ⁴ |
R513A/573 |
R513A/573 |
R513A/573 |
R513A/573 |
R513A/573 |
Sound pressure level day / night [dB(A)] ⁵ |
34/34 |
34/34 |
39/36 |
40/37 |
40/37 |
Voltage / Phases / Frequency (V/-/Hz) |
230/1/50 |
230/1/50 |
400/3/50 |
400/3/50 |
400/3/50 |
Defrosting type |
Circulating air |
Circulating air |
Circulating air |
Circulating air |
Circulating air |
Dimensions condensing unit HxWxD [mm] |
600x900x350 |
600x900x350 |
840x1030x425 |
840x1030x425 |
840x1030x425 |
Dimensions evaporator HxWxD [mm] |
455x752x430 |
455x752x430 |
455x1212x430 |
455x1212x430 |
455x1672x430 |
¹ Condensing unit, Evaporation temperature t₀ 0°C; ambient temperature + 32°C / 43°C; evaporator superheat 10K; influences of installation location and other refrigeration circuit components must be considered independently
² Basis of calculation for room size: Room temperature +8°C, Ambient temperature +25°C, heat extraction from goods 15K, operating time 16 h/day, goods handling 1/7 per day, inspection and lighting 0.5 h / day
³ Max. Compressor inlet superheat 20K
⁴ Based on AR5 / IPCC
⁵ Condensing unit, A-weighted equivalent sound pressure level at a distance of 10m
Viessmann is een van Europa’s leidende producenten op het gebied van commerciële koeloplossingen en staat bekend om zijn energiezuinige en duurzame koeling samen met het gebruiks- en onderhoudsgemak. Viessmann’s Tecto producten en service portfolio omvat zowel remote als plug-in meubels, koelcellen, koeloplossingen alsmede accessoires en gerelateerde diensten. De koelproducten worden geproduceerd in Viessmann’s fabrieken in Duitsland en Finland. Zij worden vertegenwoordigd door verkoopkantoren in 18 landen door heel Europa, ondersteunt door een uitgebreid netwerk van lokale partners.